In comparison to EN 13141-8:2014, the title is modified to be more in
adequacy with the content of the document but the scope is unchanged.
This European Standard specifies the laboratory test methods and test requirements for the testing of
aerodynamic, thermal, acoustic and the electrical performance characteristics of non‐ducted mechanical
supply and exhaust ventilation units used in single dwellings.
The purpose of this document is not to consider the quality of ventilation but to test the performance of
the equipment.
In general, a ventilation unit contains:
— fans for mechanical supply and exhaust;
— air filters;
— air‐to‐air heat exchanger for heat and possibly humidity recovery;
— control system;
— inlet and outlet grilles.
Such equipment can be provided in more than one assembly, the separate assemblies of which are
designed to be used together.
Such equipment can contain alternating heat exchangers which provide separate supply and exhaust air
flows.
In certain cases, i.e. alternating ventilation unit, the manufacturer may declare that the equipment can be
installed in such a way that it serves more than one room. For the purpose of this document, these
products are assessed in a single room.
This document does not deal with ducted units or units with heat pumps.
Safety requirements are given in EN 60335‐2‐40 and EN 60335‐2‐80.
Registration number (WIID)
67023
Scope
In comparison to EN 13141-8:2014, the title is modified to be more in
adequacy with the content of the document but the scope is unchanged.
This European Standard specifies the laboratory test methods and test requirements for the testing of
aerodynamic, thermal, acoustic and the electrical performance characteristics of non‐ducted mechanical
supply and exhaust ventilation units used in single dwellings.
The purpose of this document is not to consider the quality of ventilation but to test the performance of
the equipment.
In general, a ventilation unit contains:
— fans for mechanical supply and exhaust;
— air filters;
— air‐to‐air heat exchanger for heat and possibly humidity recovery;
— control system;
— inlet and outlet grilles.
Such equipment can be provided in more than one assembly, the separate assemblies of which are
designed to be used together.
Such equipment can contain alternating heat exchangers which provide separate supply and exhaust air
flows.
In certain cases, i.e. alternating ventilation unit, the manufacturer may declare that the equipment can be
installed in such a way that it serves more than one room. For the purpose of this document, these
products are assessed in a single room.
This document does not deal with ducted units or units with heat pumps.
Safety requirements are given in EN 60335‐2‐40 and EN 60335‐2‐80.