The European Standard specifies, dimensions, materials and performance requirements (including methods of test) for expansion groups, of nominal sizes from DN 10 to DN 25, having working pressures from 0,1 MPa (1 bar) to 1,0 MPa (10 bar).
Expansion groups are intended for fitting to the cold water supply of storage water heaters, having a maximum distribution temperature of 95 °C, for all energy sources.
Expansion groups limit pressure, in the water heater to which they are fitted, that is produced by thermal expansion of the water, prevent the backflow of water into the main circuit and prevent the discharged water to get into contact with the water in the water heater.
Expansion groups do not control temperature and alone do not constitute the protection required for storage water heaters.
NOTE The use of the device specified in this Standard does not override the need to use controls (e.g. thermostats and thermal cut-outs) which act directly on the power sources of water heaters.
Registration number (WIID)
40515
Scope
The European Standard specifies, dimensions, materials and performance requirements (including methods of test) for expansion groups, of nominal sizes from DN 10 to DN 25, having working pressures from 0,1 MPa (1 bar) to 1,0 MPa (10 bar).
Expansion groups are intended for fitting to the cold water supply of storage water heaters, having a maximum distribution temperature of 95 °C, for all energy sources.
Expansion groups limit pressure, in the water heater to which they are fitted, that is produced by thermal expansion of the water, prevent the backflow of water into the main circuit and prevent the discharged water to get into contact with the water in the water heater.
Expansion groups do not control temperature and alone do not constitute the protection required for storage water heaters.
NOTE The use of the device specified in this Standard does not override the need to use controls (e.g. thermostats and thermal cut-outs) which act directly on the power sources of water heaters.