This document specifies requirements, design and test methods for factory made thermally insulated bonded fitting assemblies for directly buried district cooling distribution systems, comprising a service fitting from DN 15 to DN 1200, rigid polyurethane foam insulation and a casing of polyethylene.
The fitting assembly can also include the following additional elements: measuring wires, spacers and diffusion barriers.
This document covers the following fitting assemblies: bend, tee, reducer, cap and anchor.
This document applies only to insulated fitting assemblies, for continuous operation with water at various temperatures (1 to 30) °C and a maximum operation pressure of 25 bar.
The design is based on an expected service life with continuous operation of a minimum 50 years.
NOTE An expected service life of 50 years presupposes that treated water is used.
Reģistrācijas numurs (WIID)
69251
Darbības sfēra
This document specifies requirements, design and test methods for factory made thermally insulated bonded fitting assemblies for directly buried district cooling distribution systems, comprising a service fitting from DN 15 to DN 1200, rigid polyurethane foam insulation and a casing of polyethylene.
The fitting assembly can also include the following additional elements: measuring wires, spacers and diffusion barriers.
This document covers the following fitting assemblies: bend, tee, reducer, cap and anchor.
This document applies only to insulated fitting assemblies, for continuous operation with water at various temperatures (1 to 30) °C and a maximum operation pressure of 25 bar.
The design is based on an expected service life with continuous operation of a minimum 50 years.
NOTE An expected service life of 50 years presupposes that treated water is used.