This document specifies methods for calculation of the thermal and fluid dynamic characteristics of chimneys serving more than one combustion appliance.
This part of prEN 13384 covers the following cases:
a) where the chimney is connected with more than one connecting flue pipe from individual or several combustion appliances in a multi-inlet arrangement;
b) where the chimney is connected with an individual connecting flue pipe connecting more than one combustion appliance in a cascade arrangement; or
c) where the balanced flue chimney consists of a collective air supply duct serving the combustion air to more than one combustion appliance. Each combustion appliance is connected to an individual flue duct located inside the collective air supply duct to the outlet. Every individual flue duct has a temperature class not exceeding T120, a pressure class of P1, M1 or H1 and a sootfire class of O.
The case of multiple inlet cascade arrangement is covered by the case a).
This part of prEN 13384 deals with chimneys operating under negative pressure conditions (there can be positive pressure condition in the connecting flue pipe) and with chimneys operating under positive pressure conditions and is valid for chimneys serving combustion appliances for liquid, gaseous and solid fuels.
For positive pressure chimneys (case a), b) and c)) this part only applies if any combustion appliance which is out of action can be positively isolated to prevent flue gas back flow.
This part of EN 13384 does not apply to:
- chimneys with different thermal resistance or different cross-section in the various chimney segments. This part does not apply to calculate energy gain;
- chimneys with open fire places, e.g. open fire chimneys or chimney inlets which are normally intended to operate open to the room;
- chimneys which serve different kinds of combustion appliances regarding natural draught, fan assisted, forced draught or combustion engine. Fan assisted combustion appliances with draught diverter between the fan and the chimney are considered as natural draught combustion appliances;
- chimneys with multiple inlets from more than 5 storeys. (This does not apply to balanced flue chimney.);
- chimneys serving combustion appliances with open air supply through ventilation openings or air supply ducts, which are not installed in the same air supply pressure region (e.g. same side of building).
Reģistrācijas numurs (WIID)
77531
Darbības sfēra
This document specifies methods for calculation of the thermal and fluid dynamic characteristics of chimneys serving more than one combustion appliance.
This part of prEN 13384 covers the following cases:
a) where the chimney is connected with more than one connecting flue pipe from individual or several combustion appliances in a multi-inlet arrangement;
b) where the chimney is connected with an individual connecting flue pipe connecting more than one combustion appliance in a cascade arrangement; or
c) where the balanced flue chimney consists of a collective air supply duct serving the combustion air to more than one combustion appliance. Each combustion appliance is connected to an individual flue duct located inside the collective air supply duct to the outlet. Every individual flue duct has a temperature class not exceeding T120, a pressure class of P1, M1 or H1 and a sootfire class of O.
The case of multiple inlet cascade arrangement is covered by the case a).
This part of prEN 13384 deals with chimneys operating under negative pressure conditions (there can be positive pressure condition in the connecting flue pipe) and with chimneys operating under positive pressure conditions and is valid for chimneys serving combustion appliances for liquid, gaseous and solid fuels.
For positive pressure chimneys (case a), b) and c)) this part only applies if any combustion appliance which is out of action can be positively isolated to prevent flue gas back flow.
This part of EN 13384 does not apply to:
- chimneys with different thermal resistance or different cross-section in the various chimney segments. This part does not apply to calculate energy gain;
- chimneys with open fire places, e.g. open fire chimneys or chimney inlets which are normally intended to operate open to the room;
- chimneys which serve different kinds of combustion appliances regarding natural draught, fan assisted, forced draught or combustion engine. Fan assisted combustion appliances with draught diverter between the fan and the chimney are considered as natural draught combustion appliances;
- chimneys with multiple inlets from more than 5 storeys. (This does not apply to balanced flue chimney.);
- chimneys serving combustion appliances with open air supply through ventilation openings or air supply ducts, which are not installed in the same air supply pressure region (e.g. same side of building).